Customer requirements
The customer specified a distributed remote I/O architecture and a warm backup for the PLC. The customer also provided a conveyor manifest that listed the variable frequency drives (VFDs) to be used.
Design process
I started from the customer's specification, the conveyor manifest and the mechanical layout of the conveyors. I used the company's past projects as the basis for the design and for selecting parts. The work proceeded in this order:
- Device layout drawings
- 480 V power distribution
- Control I/O wiring diagrams
- Emergency-stop zones
- Network
- Field 24 VDC wiring
Device layout
I was given the mechanical layout of the conveyors. On it I placed the electrical devices: the control stations required by the specification, the photoeyes, the shaft encoders, the motors and their drives, and the motor safety disconnects. The layout drawings also show the boundaries of the emergency-stop zones.
480 V power distribution
I designed the power distribution from the incoming 480 V service to each load:
- Incoming service. A main disconnect with monitoring of the incoming supply.
- Motor feeds. The drives are mounted at the conveyors and are fed in groups from the panel. I sized the protection for each group from the full-load current of its motors, and wired the status of each breaker to the PLC.
- Local disconnects. Each motor has its own safety disconnect at the conveyor.
- Control power. A control transformer provides 120 V and a power supply provides 24 VDC, each sized for its loads.
I also determined the panel's full-load current and short-circuit current rating for the nameplate.
Control I/O
The warm backup requirement applied to the two PLC processors and the Ethernet I/O adapter. The panel has a primary and a backup processor, and the I/O inside the panel is on an Ethernet I/O adapter that either processor can control, so the backup can take over without any change to the wiring.
The panel I/O is used mainly for the operator controls on the door and for monitoring the panel itself, including the breakers, the power supply and the network equipment, so that a fault inside the panel can be reported.
The 24 VDC supply is divided into separately protected circuits, so that a fault on one circuit does not remove power from the others.
Remote I/O
Most field signals are brought in through the drives. Each drive is mounted at its conveyor and has its own inputs, which take that conveyor's photoeye and the status of its motor safety disconnect. Where a location needed more I/O than the drive's onboard inputs could take, I added a field I/O block on the network. The blocks connect the control stations and the remaining photoeyes, shaft encoders and disconnects. I also prepared the cable lists for all of the M12 connections on the I/O blocks.
Emergency-stop zones
Most airports require safety relays for emergency-stop zones and do not permit safety signals to be carried over Ethernet, so the emergency-stop system is hardwired and separate from the control network.
- Zones. The conveyors are divided into zones, each with its own safety relay. The emergency-stop pushbuttons in a zone are wired to that zone's relay.
- Stopping the motors. Each safety relay is wired to the safety inputs of the drives in its zone, so the drives stop their motors without relying on the PLC or the network.
- Zone boundaries. A conveyor that sits between two zones stops when either zone is stopped.
- Adjacent equipment. The emergency-stop circuit is interlocked with an existing panel at the point where the two systems meet.
- Monitoring. The state of each zone is reported to the PLC.
Network
A network switch in the panel connects the processors, the panel I/O, the operator display and the link to the existing system.
The drives and field I/O blocks at the conveyors are connected in rings. Each ring leaves the panel, passes from device to device along the conveyors, and returns to the panel, so a single broken cable does not disconnect the devices beyond it.
Field 24 VDC wiring
The drives at the conveyors need 24 VDC control power in addition to their 480 V feed. The panel supplies it on separately protected circuits that run from conveyor to conveyor, together with the emergency-stop wiring for the zone.
Because these circuits run the length of the conveyor lines, I calculated the voltage drop along each run to determine how many drives could be supplied from a single run before the voltage at the far end fell too low.
At each conveyor a junction box distributes the wiring to the drive. I defined a small number of standard junction box types, each with its own layout drawing and bill of materials, so the boxes can be built as repeatable assemblies.
Integration with existing equipment
The panel had to communicate with an existing panel that uses Modbus TCP, while the new system uses EtherNet/IP. I connected the two through an Anybus module.
Drawing package
The finished drawing set is more than 70 sheets, produced in AutoCAD Electrical:
| Sheets | Content |
|---|---|
| Device layout | Control devices, motors and drives, and emergency-stop zones on the conveyor layout |
| Power distribution | 480 V, 120 VAC and 24 VDC distribution |
| Emergency stop | Safety relay circuits for the panel and each zone |
| PLC I/O | Rack layout and module wiring; one sheet for the field-mounted I/O at each conveyor |
| Network | Panel network and field network |
| Panel layout | Exterior, interior, terminal detail, panel tags and bill of materials |
| Field assemblies | Control station and junction box layouts, each with a bill of materials |
| Field wiring | 24 VDC and emergency-stop wiring between conveyors; device connection details |